Broad-Based Black Economic Empowerment Act (B-BBEE Act)
Act 53 of 2003
Provides the empowerment-compliance context often used in public-sector supplier evaluation.
Relevant because this is a South African public-sector procurement opportunity.
Documents available on tender detail page
Tender Type
Request for Bid(Open-Tender)
Delivery Location
Arnot Power Station - Arnot Power Station - RIETKUIL - 1087
Organization Type
GOVERNMENT
Published
22 Jul 2026
OCDS Reference
ocds-9t57fa-163214
This tender is for the upgrade of medium voltage (mv) switchgear at eskom's arnot power station over a 3-year period. IT targets suppliers capable of delivering compliant electrical services, including cable and switchgear solutions, in line with eskom's technical standards and statutory requirements.
Continue with tenders sharing this issuer, category, or province.
Return to this tender’s issuing organisation, province, or category.
Continue with tenders sharing this issuer, category, or province.
Date & Time
Friday, 21 August 2026 - 10:00
Venue
Arnot Power Station
IT is estimated that tenderers must have a construction industry development board (CIDB) contractor grading of 8ep or 8me or higher
Categories
Request for Bid(Open-Tender)
Arnot Power Station - Arnot Power Station - RIETKUIL - 1087
AI Document Analysis Stages
Important Dates
Source: Eskom's (SHEQ) Policy Poster (32-727) final_rev 10.pdf (unknown)22 Jul
2026
Tender Published
Tender was published
21 Aug
2026
Closing Date
Tender closing date
These references help suppliers understand the public-procurement framework around this opportunity. They are generated from the tender category, issuing organisation type and procurement context.
These rules commonly apply to South African public-sector procurement.
Act 53 of 2003
Provides the empowerment-compliance context often used in public-sector supplier evaluation.
Relevant because this is a South African public-sector procurement opportunity.
Act 108 of 1996 (s217)
This is general procurement context, not legal advice. Always verify requirements in the official tender documents and issuing authority notices.
MV Switchgear Technical Evaluation Criteria Rev 2..pdf
Eskom seeks a contractor for a 3-year project to replace obsolete and unsafe medium voltage (MV) switchgear at Arnot Power Station in Mpumalanga. The scope includes full removal of old equipment, design, supply, installation, testing, and commissioning of new, compliant MV switchgear.
240-56227573 Air-Insulated Withdrawable AC Metal-Enclosed Switchgear Controlgear for 1kV to 52kV.pdf
Eskom tender for the provision of Outside Plant MV Switchgear Upgrade at Arnot Power Station for 3 years. The document is a technical standard (240-56227573 Revision 2) specifying requirements for new air-insulated, withdrawable, AC metal-enclosed switchgear and controlgear for rated voltages above 1kV up to and including 52kV for indoor installations in Eskom Generation power plants.
Invitation to Tender (ITT) - Switch Gear Upgrade.pdf
Eskom invites tenders for a 3-year contract to upgrade Outside Plant Medium Voltage (MV) Switchgear at Arnot Power Station. The tender is open, uses the NEC3 Engineering & Construction Contract, and requires electronic submission via Eskom's e-tendering portal by 21 August 2026.
MV Switchgear Outside Plant 2026.zip
The tender is for the provision of Outside Plant MV Switchgear Upgrade at Arnot Power Station over a 3-year period. The project involves replacing outdated and unsafe MV switchgear, battery chargers, and associated systems to improve safety, reliability, and maintainability. The scope includes design, manufacturing, supply, installation, testing, commissioning, and handover of new MV switchgear, DC chargers, batteries, and support structures, as well as decommissioning and removal of existing equipment. The new switchgear must comply with Eskom standards and include modern protection schemes, HVAC systems, and interfaces with existing control and instrumentation systems.
240-56227589 list of approved electronic devices.pdf
This document is Eskom's 'List of Approved Electronic Devices to be used on Eskom Power Stations Standard' (Revision 4). It is not the tender document itself but a critical referenced technical standard. The actual tender is for the provision of Outside Plant MV Switchgear Upgrade at Arnot Power Station for 3 years. This standard defines the approved manufacturers, models, and functions of electronic devices (protective relays, IEDs, controllers, meters, etc.) that may be used in Eskom Generation projects, including the referenced tender work.
Tender Advert Template Switchgear.pdf
Eskom invites tenders for a 3-year contract to upgrade Outside Plant MV Switchgear at Arnot Power Station. The tender requires CIDB registration, has a clarification meeting scheduled, and a closing date in August 2026.
240-77471499 Annexure B (3).docx
This tender document outlines ESKOM's requirements for the provision of Outside Plant MV Switchgear Upgrade at Arnot Power Station over a 3-year period, with a strong emphasis on Occupational Health and Safety (OHS) compliance and contractor management responsibilities.
Tender Advert Template MV Switchgear upgrade.pdf
Eskom invites tenders for a 3-year contract to upgrade the Outside Plant MV Switchgear at Arnot Power Station. The tender requires CIDB registration and has a clarification meeting scheduled.
240-56357424 MV and LV Switchgear Protection Standard (Rev 2.1).pdf
This tender document comprises two primary components: 1) A memorandum from Eskom stating that the MV (Medium Voltage) protection requirements in the standard '240-56357424: MV and LV Switchgear Protection Standard' have been superseded by a new standard ('240-143485806 Generation auxiliary plant medium voltage protection standard'). The old combined standard no longer governs MV protection. 2) The detailed, now-partially-superseded standard itself, which outlines comprehensive technical requirements for the protection of MV and LV electrical plant, including protection philosophies, relay functions, setting principles, and specific requirements for switchgear, cables, transformers, and motors.
240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdf
This document is not the tender itself but an Eskom technical standard (Earthing and Lightning Protection Standard, Revision 2) that defines the mandatory design, installation, and testing requirements for earthing and lightning protection systems within Eskom Generation power stations. It will be a critical compliance reference for any contractor bidding on the 'Outside Plant MV Switchgear Upgrade at Arnot Power Station' tender, as the work must adhere to this standard.
240-68099512 Form A_Cat 1_ Rev 9.docx
The tender is for the provision of Outside Plant MV Switchgear Upgrade at Arnot Power Station over a 3-year period. It is issued by Eskom and requires compliance with Eskom Supplier Quality Requirements (Specification 240-105658000) and ISO 9001 standards. The tenderer must acknowledge and accept these requirements by completing and signing the provided form.
240-77471651 Annexure C 1.docx
Eskom tender for a 3-year Outside Plant MV Switchgear Upgrade at Arnot Power Station. The document is primarily an OHS (Occupational Health and Safety) evaluation checklist, indicating that safety compliance is a critical and mandatory component of the tender assessment.
Eskom's (SHEQ) Policy Poster (32-727) final_rev 10.pdf
ESKOM is seeking a contractor to provide Outside Plant MV Switchgear Upgrade services at Arnot Power Station for a 3-year period. The tender involves upgrading medium-voltage switchgear infrastructure located outside plant buildings.
ECC Outside plant MV switchgear upgrade.pdf
Eskom seeks a contractor for a 3-year Outside Plant MV Switchgear Upgrade at Arnot Power Station using NEC3 Engineering & Construction Contract Option A (priced contract with activity schedule). The contract includes design, installation, and commissioning of 11kV switchgear, with key dates for design and completion by 31 December 2030.
240-143485806 Gx MV Protection std.pdf
This document is not a tender solicitation but Eskom's internal technical standard (240-143485806) for Medium Voltage Protection in Generation Auxiliary Plant. It defines the protection philosophy, design principles, and technical specifications for MV protection systems across Eskom power stations, including switchgear upgrades. The referenced tender is for a 3-year Outside Plant MV Switchgear Upgrade at Arnot Power Station, and this standard would govern the technical compliance of any proposed solution.
240-56030406 RMU standard.pdf
Eskom seeks a contractor for a 3-year Outside Plant MV Switchgear Upgrade at Arnot Power Station. The tender is governed by a detailed technical specification (240-56030406, Rev 2) for Ring Main Units (RMUs) and Integrated Remote Terminal Unit (IRTU) fitted RMUs for systems with nominal voltages from 3.3 kV to 33 kV (up to 36 kV). The specification standardizes requirements for new, factory-assembled RMUs for indoor/outdoor use, including protection systems, remote control, and corrosion protection.
TENDER~3.PDF
Eskom seeks a contractor for a 3-year Outside Plant MV Switchgear Upgrade project at Arnot Power Station. The tender emphasizes compliance with preferential procurement policies, including B-BBEE scoring, local content thresholds, skills development, and subcontracting to designated groups. The evaluation uses a 90/10 scoring system (90 for price, 10 for B-BBEE status), with additional mandatory SDL&I (Supplier Development, Localisation & Industrialisation) obligations that become contractual commitments.
Life-Saving Rules (2).pdf
This document is not the tender document itself but Eskom's Life-Saving Rules Standard (Revision 7). It defines six critical safety rules with zero-tolerance enforcement for all personnel (including contractors) working on Eskom sites. It is a mandatory compliance document for any contractor bidding for or working on the 'Outside Plant MV Switchgear Upgrade at Arnot Power Station' tender.
240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdf
This tender document outlines Eskom's technical requirements for control and power cables to be used in the Outside Plant MV Switchgear Upgrade at Arnot Power Station over a 3-year period. It is a controlled disclosure standard specifying cable types, specifications, installation, testing, and compliance requirements for power station applications.
To download these documents and access AI-powered analysis, visit the main tender page.
Win Eskom tenders with AI Tender Matching, technical document analysis, compliance scoring, and structured bid support for energy and engineering contracts.
Matched by category & region
Free guidance to prepare before you bid
Not sure if your business is ready for this tender? Check CSD, CIDB, and B-BBEE requirements, run a readiness assessment, and move from opportunity to submission.
Open Supplier Readiness HubLearn how to submit a winning bid with these related articles
Median Estimate
R 4 500 000
Range
Based on CIDB grading. Companies with similar profiles typically bid near the median.
* Estimates are based on historical data and do not guarantee actual award values.
💡 Want more tendering tips and strategies?
Explore Our BlogGet deep intelligence on Services: Electrical. Unlock full pricing strategies, bid frequency, and historical win rates.
We refine every tender document through these stages so you can brief your team and prepare your bid with confidence. Anything marked as "in progress" will be upgraded automatically — no action required from you.
14 April 2026
Submission Guidelines
Source: Eskom's (SHEQ) Policy Poster (32-727) final_rev 10.pdf (unknown)Returnable Documents: Not specified in the provided text.
Evaluation Criteria
Source: Eskom's (SHEQ) Policy Poster (32-727) final_rev 10.pdf (unknown)Bidders must be registered with relevant industry bodies (CIDB grading likely required). Must demonstrate previous experience with MV switchgear projects. Must have valid tax clearance certificate. Must comply with ESKOM's vendor registration requirements.
Description
Source: 240-77471651 Annexure C 1.docxTenderer’s / Supplier’s name: ………………………………………………. Tender Ref number: ………………………………….
Submission Guidelines
Source: 240-77471651 Annexure C 1.docx (unknown)Returnable Documents: The tenderer must submit the following OHS tender returnables:
Evaluation Criteria
Source: 240-77471651 Annexure C 1.docx (unknown)Mandatory eligibility is contingent on the complete and compliant submission of all listed OHS returnables (items 1-7). Failure to submit any required document, or submission in a non-compliant format (e.g., lump-sum OHS costing), will likely result in disqualification or a 'Not Recommended' evaluation. The tenderer must operate under a valid COIDA registration or equivalent.
Technical Specifications
Source: 240-77471651 Annexure C 1.docx (unknown)Tenderer’s / Supplier’s name: ………………………………………………. Tender Ref number: ………………………………….
Scope of work: ………………………………………………………………………………………………………………………
Compliance Requirements
Source: 240-77471651 Annexure C 1.docx (unknown)No specific requirements found
Description
Source: 240-56227573 Air-Insulated Withdrawable AC Metal-Enclosed Switchgear Controlgear for 1kV to 52kV.pdf (unknown)Title: Generation Air-Insulated 240-56227573 Unique Identifier: Withdrawable AC Metal- Enclosed Switchgear and Controlgear for Rated N/A Voltages above 1kV up to and including 52kV
Evaluation Criteria
Source: 240-56227573 Air-Insulated Withdrawable AC Metal-Enclosed Switchgear Controlgear for 1kV to 52kV.pdf (unknown)Suppliers must demonstrate capability to meet the extensive technical specifications. Eligibility is implicitly based on the ability to provide equipment that is type-tested to the referenced standards (SANS 62271 series, IEC standards, etc.) and the specific requirements of this Eskom Generation standard. Suppliers must submit relevant type test reports during tender to validate equipment ratings against Eskom's system conditions. The equipment and manufacturing processes must comply with referenced quality standards (e.g., ISO 9001, ISO 17025).
Technical Specifications
Source: 240-56227573 Air-Insulated Withdrawable AC Metal-Enclosed Switchgear Controlgear for 1kV to 52kV.pdf (unknown)This document contains the standard requirements of new air-insulated withdrawable AC metal-enclosed
switchgear and controlgear for rated voltages above 1kV and up to and including 52kV for indoor
installations in accordance with SANS 62271-200.
The basic requirements for design, operations and maintenance shall be defined in this standard as
applicable in the power generation plants belonging to Eskom Generation Group.
The requirements for withdrawable AC metal-enclosed switchgear and controlgear for rated voltages
above 1kV and up to and including 52kV for indoor installations in special environmental conditions such
as nuclear applications are not included in this standard. Those requirements for switchgear for
installation and use in special environmental conditions (i.e. exposure to high temperature, exposure to
high pressure, earthquakes etc.), shall be subject to additional requirements.
This standard excludes requirements for metal-enclosed switchgear used in secondary distribution in the
form of Ring Main Units (RMU). The requirements for RMUs are outlined in the Eskom Distribution
Standard 240-56030406.
This standard includes requirements for 10 to 100MVA generator circuit-breakers and it excludes
requirements for generator circuit-breakers that are rated 100 MVA and above. The requirements for
generator circuit-breakers rated above 100MVA are outlined in the Eskom Generation Standard 24056227522. This standard also excludes generator circuit-breakers intended for use in applications for
pumped storage installations.
2.1 Scope
2.1.1 Purpose
The standard describes requirements for new air-insulated withdrawable AC metal-enclosed switchgear
and controlgear for rated voltages above 1kV and up to and including 52kV for indoor installation.
In order to ensure standardisation, the withdrawable AC metal-enclosed switchgear and controlgear
covered by this standard shall be type tested, of modular design with air-insulated busbars for use on
three phase systems at a rated frequency of 50Hz.
The standard also describes requirements for generator circuit-breakers for generators rated 10 MVA to
100MVA. These generator circuit-breakers are traditionally housed in an AC metal-enclosed switchgear
and controlgear.
Components contained within the withdrawable metal-enclosed switchgear and controlgear functional
unit shall be designed, manufactured and tested in accordance with their respective relevant standards.
The manufacturer shall design and supply the necessary connections, interconnecting wiring, supporting
steelwork, holding-down bolts, guards, labels, other interfaces to structural foundations, accepted
documentation, accessories etc. required to make a complete functional assembly that comply with this
standard.
2.1.2 Applicability
This document shall apply to the Eskom Generation Group.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
2.2 Normative/informative references
Parties using this document shall apply the most recent edition of the documents listed in the following
paragraphs.
2.2.1 Normative
The following documents (all parts including any amendments) contain provisions for this standard. For
referenced standards, the latest revision of the document shall apply.
[1] 240-114967625 Operating Regulations for High-Voltage Systems.
[2] 240-75655504 Corrosion protection standard for new indoor and outdoor Eskom equipment,
components, materials and structures manufactured from steel Standard.
[3] 240-143485806 Generation Auxiliary Plant MV Protection Standard.
[4] 240-56357424 MV and LV Switchgear Protection Standard.
[5] 240-56227589 List of Approved Electronic Devices to be used on Eskom Power Stations.
[6] 240-64685228 Generic Specific for Protection Intelligent Electronic Devices (IEDs)
[7] 240-150642762 Generation Plant Safety Regulations.
[8] 240-71432150 Plant Labelling Standard.
[9] 240-86973501 Engineering Drawing Standard - common requirements
[10] 240-56065202 Switchgear training requirements from original equipment manufacturers standard.
[11] TBA Engineering Drawing Symbol Standard.
[12] 0.00-002839 MV and LV Switchgear Outdoor Isolator Padlock.
[13] 0.00-10341-01 MV and LV Switchgear Lugs and Terminals.
[14] 0.00-10341-02 MV and LV Switchgear Pre-Insulated Lugs and Sleeves.
[15] 0.00-10341-03 MV and LV Switchgear Wiring and Termination.
[16] 0.00-10341-04 MV and LV Switchgear Circuit Function Letters.
[17] 0.00-10343-01 MV, LV and DC Switchgear Labels and Nameplate Details English Designation
Only Arrangement Diagram.
[18] 0.00-10343-02 General Labels & Nameplate Details Arrangement Diagram.
[19] OHS Act Occupational Health and Safety Act (Act ) and Regulations.
[20] SANS 1091 National Colour Standards.
[21] SANS 1574 Electric Cables- Flexible Cords and Flexible Cables.
[22] SANS 10142-2 The Wiring of Premises Part 2: MV Installations above 1kV a.c. not exceeding
22kV a.c. and upto and including 3 MVA installed capacity.
[23] SANS 876 Cable terminations and live conductors within air-filled enclosures (insulation co-
ordination) for rated a.c. voltages from 7.2 kV up to and including 36 kV.
[24] SANS 60529 Degrees of Protection Provided by Enclosures (IP Code)
[25] SANS 61000 Electromagnetic Compatibility (all relevant parts).
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
[26] SANS 61243-5 Live working – Voltage Detectors – Part 5: Voltage Detecting Systems (VDS).
[27] SANS 62271-1 High-Voltage Switchgear and Controlgear – Part 1: Common Standards.
[28] SANS 62271-100 High-Voltage Switchgear and Controlgear – Part 100: High-Voltage
Alternating-Current Circuit-Breakers.
[28] SANS 62271–102 High-Voltage Switchgear and Controlgear – Part 102: Alternating Current
Disconnectors and Earthing Switches.
[29] SANS 62271–200 High-Voltage Switchgear and Controlgear – Part 200: AC Metal-Enclosed
Switchgear and Controlgear for Rated Voltages above 1 kV and up to and
including 52 kV.
[30] SANS 62271-307 High-Voltage Switchgear and Controlgear – Part 200: Guidance for the
extension of validity of type tests of AC metal and Solid Insulation Enclosed
Switchgear and Controlgear for rated voltages above 1kV and up to and including
52kV.
[31] SANS 61869-1 Instrument transformers Part 1: General requirements.
[32] SANS 61869-2 Instrument transformers Part 2: Additional requirements for current transformers.
[33] SANS 61869-3 Instrument transformers Part 3: Additional requirements for inductive voltage
transformers.
[34] SANS 1019 Standard Voltages, Currents and Insulation Levels for Electricity Supply.
[35] SANS 61508 Functional Safety of Electrical/electronic/programmable Electronic Safety-related
Systems. All Parts
[36] SANS 61511 Functional Safety - Safety Instrumented Systems for the Process Industry Sector.
All Parts.
[37] SANS 1195 Busbars.
[38] SANS 1411-1 Materials of Insulated Electric Cables and Flexible Cords: Part 1: Conductors.
[39] SANS 61213 Mechanical Cable Glands.
[40] SANS 60060 High-Voltage Test Techniques.
[41] SANS 60269 Low-Voltage Fuses.
[42] SANS 60947 Low Voltage Switchgear and Controlgear. All parts
[43] SANS 61238-1 Compression and Mechanical Connections for Power Cables for Rated Voltages
up to 30 kV(Um=36kV) Part 1: Test methods and requirements.
[44] IEC 60051 Direct-Acting Analogue Electrical Measuring Instruments and their Accessories.
[45] IEC 60688 Electrical Measuring Transducers for Converting AC and DC Electrical Quantities
to Analogue or Digital Signals.
[46] IEC/IEEE 62271-37-013 High-Voltage Switchgear and Controlgear – Part 37-013: Alternative –
current generator circuit-breakers.
[47] IEEE Std C37.013a Standard for AC High Voltage Generator Circuit-breakers Rated on a
Symmetrical Current Basis – Amendment 1: Supplement for Use with Generator
Rated 10-100 MVA.
[48] ISO 17025 General Requirements for the Competence of Testing and Calibration Laboratories
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
[49] ISO 9001 Quality Management Systems.
[50] CDA Publication 22 Copper Development Association (CDA), Publication 22, Copper for
busbars.
[51] IEC 60038 Standard Voltages.
[52] IEC 60518 Dimensional standardisation of terminals for high-voltage switchgear and
controlgear.
[53] EPRI 10003471 Electrical Connector Guideline.
2.2.2 Informative
Not applicable.
2.3 Definitions
The definitions contained in SANS 62271 shall apply. The following are the definitions of specific
uncommon terms used in the document
Definition Description
Abnormal Power Supply Conditions whereby switchgear is operated within the design and
System Conditions testing requirements but outside the normal system voltage and
frequency but within the fault current specified.
Behind-Closed-Door This refer to the design of switchgear where the circuit-breaker
Operation compartment is such that the circuit-breaker is withdrawable and can
be moved from the service position to the disconnected or test
position and vice versa with the front door of the circuit-breaker
compartment closed and locked.
Busbar Extension Dummy A panel which is only contain the busbar functional compartment, and
Panel is designed and installed between two adjacent panels to provide
spacing for cable termination alignment. (See definition of Panel
below)
Earth bar Metallic bar forming part of the switchboard and used as a conductor
for grounding and or earth path circuits as may be connected with it.
Electrical Life of Components The electrical and mechanical designed operational life of equipment
and components, in terms of the number of electrical operations,
mechanical operations, age, etc.
Exhaust Duct Mechanism used to evacuate gasses generated during an internal arc
to the outside of the room. This shall be installed at the top of the
switchboard and it shall be connected to the explosion vent and shall
have a type tested sealed lid.
Explosion vent Mechanism used to discharge gasses from functional unit enclosure
into an exhaust duct to relieve the pressure generated during an
internal arc. This shall normally be installed at the top of the enclosure
and shall form part of the functional unit.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
Definition Description
IAC AFLR Internal arc classification for type A (operator safety) accessibility for
the front side, lateral side and rear side of the panel
Joggle Chamber Custom designed metal enclosed panel used to align the busbars of
different types of metal-enclosed switchgear
Mechanical Life The life expectancy of the component which shall be determined by
the mechanical operations of the component. The mechanical
operational life expectancy shall be determined irrespective of the
electrical operational load.
Panel General term referring to a functional unit of metal-enclosed
switchgear in accordance with SANS 62271-200.
Specialised tools Any purpose-built tools that are necessary to carry out major (or
specialised) maintenance on a circuit-breaker and its components
Switchboard A complete switchgear assembly consisting of number of switchgear
panels (switchgear panels include incomer panels, feeder panels,
bus-section panels where cables are used to connect two bus-section
breakers, VT panels, etc.).
2.3.1 Disclosure Classification
Controlled disclosure: controlled disclosure to external parties (either enforced by law, or
discretionary).
2.4 Abbreviations
AC Alternating Current
AFLR A-(operator safety), Front, Lateral, Rear
CoE Centre of Excellence
CSMES SC Cable Systems and Metal Enclosed Switchgear Study Committee
CT Current Transformer
DC Direct Current
EPRI Electric Power Research Institute
HMI Human Machine Interface
HRC High Rupturing Current/Capacity
IAC Internal Arc Classified
IEC International Electrotechnical Commission
IEEE Institute of Electrical and Electronics Engineers
IP International Protection code
ISO International Organization for Standardization
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
LSC Loss of Service Continuity
LV Low Voltage
MCB Miniature Circuit-Breaker
MES CG Metal Enclosed Switchgear Care Group
MV Medium Voltage
NPS Negative Phase Sequence
ORHVS Operating Regulations of High Voltage Systems
PILC Paper Insulated Lead Covered
PM Partitions Metallic
PPS Positive Phase Sequence
RMU Ring Main Unit
SANS South African National Standards
VDS Voltage Detection System
VT Voltage Transformer
XLPE Cross-linked Polyethylene
2.5 Roles and responsibilities
Generation Asset Management is the custodian of the standard.
Generation power stations should ensure that acquisition of all new MV switchgear is done
in accordance to the provisions of this document.
This document shall be used in conjunction with the technical specification.
2.6 Process for monitoring
None
2.7 Related/supporting documents
[54] 240-93576770 Technical A&B Schedule Template
[55] 240-93576642 Compliance Schedule Template
[56] 240-77300784 MV Switchgear Schedules Template
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
Enclosed switchgear and controlgear
3.1 Ratings and operating conditions
3.1.1 Panel Ratings
a) The ratings selected for the switchgear and controlgear, their operating devices and the auxiliary
equipment shall be in accordance with SANS 62271-200, and shall be provided in each project
specific Switchgear Schedules (240-77300784) and Technical Schedule A&B (240-93576770).
b) The associated temperature rise for the rated normal current specified in each Technical Schedule
A&B and Switchgear Schedule shall be in accordance with SANS 62271-200. The panel types shall
be fully type tested at the specified current ratings.
c) For motor starters, the temperature rise current ratings shall take into account the impact of the
motor starting current and the number of starts per hour specified.
3.1.2 Ratings for Switching Devices
a) The circuit-breaker shall be capable of continuously carrying the circuit-breaker current rating as
specified and at the specified altitude for an ambient temperature of 40oC.
b) All assigned current ratings relate to the circuit-breaker in the in-service position within the fully
assembled and functional unit.
c) The circuit-breaker shall be capable of interrupting, making, latching against and able to withstand
the specified fault duties at the maximum specified voltage.
d) The electrical endurance for the circuit-breaker shall be classified as Class E2 in accordance with
SANS 62271-100 without reclosing, unless otherwise specified for special applications.
e) The mechanical endurance for the circuit-breaker shall be classified as Class M2 in accordance with
SANS 62271-100.
f) The electrical endurance for Earthing devices shall be Class E2 in accordance with SANS 62271-
102, as a minimum.
g) The mechanical endurance for Earthing devices shall be Class M1 in accordance with SANS 62271-
h) The short-circuit withstand current rating and insulation level of an earthing device shall match that
of the panel. This excludes the special installations such as small generating plant (less than
100MVA) where power evacuation system consists of metal enclosed switchgear.
i) The connection between the earthing device and the panel earth bar shall be designed to withstand
the panel short-circuit withstand rating for same duration.
3.1.3 System Characteristics and Operating Conditions
The following system characteristics and operating conditions may be experienced on Eskom
Generation Plants where medium voltage withdrawable metal enclosed switchgear and controlgear will
be installed. It is therefore required that during tender submissions, suppliers need to indicate and submit
where applicable, the relevant SANS/IEC type test reports that can be used to validate equipment
ratings against these system characteristics and operating conditions.
a) Main power system normal power supply conditions may occur simultaneously as follows:
Voltage: ± 5%
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
Negative Phase Sequence (NPS) voltage up to 0.02 of nominal Positive Phase Sequence (PPS)
voltage
The Zero Phase Sequence Voltage component can be up to 1% of the PPS component.
b) Circuit-breaker auxiliary coils shall be functional under the following conditions for both AC and DC
applications:
Shunt closing release – between 85% and 110% of the rated supply voltage.
Shunt opening release – between 85% and 110% of the rated supply voltage.
Under-voltage release - below 35% of the rated supply voltage.
c) The harmonic distortion of the supply voltage under normal operation shall be as follows:
The Total Harmonic Distortion (THD) of the voltage can be up to 5% of the fundamental
component.
The voltage waveform can contain harmonic components up to the 100th harmonic.
The amplitude of any individual component can be up to 1% of the fundamental component.
d) The amplitude and duration of temporary abnormal voltage operating characteristics which can
occur on the power supply shall be as follows:
Short Duration Abnormal Conditions: Short duration under voltage conditions arise either due to
a loss of supply or the supply voltage being depressed due to a short circuit on the network.
Loss of Power Supply:
i. When the supply is disconnected, the supply voltage either drops rapidly to 0% of
nominal value or it is sustained at low amplitude at a reduced frequency because of back
generation of electrical drives.
ii. The initial voltage amplitude during these conditions is less than 80% of nominal value
and decays with a time constant of up to 1.5 seconds.
iii. The time duration from loss of supply until supply restoration is between 1 second and
2.5 seconds.
3.1.4 Switchgear Operating Conditions
a) The switchgear shall comply with the power station operating conditions and with the operating
requirements of 240-114967625: Operating Regulations for High-voltage Systems.
b) Under normal and abnormal conditions, in the events the following may occur during which all the
safety requirements of the switchgear and controlgear shall be met;
A fault can occur when moving a withdrawable component (e.g. a circuit-breaker) from the
disconnected, earthed or test position to the service position and vice versa
An earth switch can be applied onto a live power circuit
A low voltage compartment investigation can be performed while the functional unit is live
VTs’ can be racked in/out with the switchboard energised
A cable can be terminated in an isolated cable compartment whilst the busbars of the isolated
compartment panel and adjacent cable compartments are live
Busbar VT panel can be racked out and accessed whilst the busbars and adjacent circuit-breaker
compartments are alive.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.2 Panel design and construction
3.2.1 Service Conditions
The normal service conditions for indoor switchgear and controlgear specified in SANS 62271-1 shall
apply. The following additional specific requirements shall be taken into account:
a) A minimum ambient air temperature of -5 0C;
Note: A maximum ambient air temperature of 40 0C is applicable, in accordance with the ‘normal’
service conditions for indoor switchgear as specified in SANS 62271-1.
b) The switchgear shall be installed up to altitudes of 1800 m;
Note: Due (in part) to the fact that the switchgear and controlgear shall be used up to altitudes of 1800
m AMSL (Above Mean Sea Level), higher insulation withstand levels shall be specified in project
specific Switchgear Schedules (240-77300784). No further altitude correction factors are
therefore required for altitudes above 1000 m AMSL in accordance with SANS 62271-1.
3.2.2 General Requirements
a) The switchgear and controlgear shall be of indoor use, air-insulated, metal-enclosed and internal arc
classified in accordance with SANS 62271-200.
b) The switchgear and controlgear shall be internal arc classified AFLR for 1 second in accordance
with SANS 62271-200.
c) The switchgear and controlgear shall be of behind-closed-door operation i.e circuit-breaker
compartment door shall not be part of the circuit-breaker.
d) The switchboards shall be of modular designs that allow for the subsequent addition of identical
panels.
e) The switchgear and controlgear shall be clearly marked with the ratings to which the equipment has
been type tested. This rating shall be in the nameplate.
f) Design information relating to the type tested and routine tested components and moulded
components (i.e. spouts, bushings, insulators) shall be made available i.e. during tendering to clarify
the materials, manufacturing method, design and manufacturing location for these components.
3.2.3 Panel Architecture
Single busbar design is required for withdrawable indoor metal enclosed switchgear and shall include the
following defined panels (functional units):
a) “Incomer” panels incorporating a withdrawable three-pole operated circuit-breaker, cable earthing
switch and cable compartment fitted with CTs, VTs and VDS;
b) “feeder” panels incorporating a withdrawable three-pole operated circuit-breaker, cable earthing
switch and cable compartment fitted with CTs and VDS;
c) “bus-section” and “interconnector) panels incorporating a withdrawable three-pole operated circuit-
breaker, CTs, VTs and VDS on both busbar sections; and
d) “VT” panels incorporating a withdrawable VT and busbar earthing switch.
Note: Switchgear schedule (240-77300784) shall indicate the required panels for a specific project.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.2.4 Segregation of Compartments
3.2.4.1 General
As a minimum, separate compartments shall be provided for the different panels forming a switchboard
as follows:
Circuit-breaker compartment
Main busbar compartment
Low voltage compartment
Power cable compartment
Busbar earthing device compartment
VT compartment
3.2.4.2 Low Voltage Compartment
a) The low voltage compartment shall be located at the front and top position of the functional unit.
b) The compartment shall be designed to house all equipment required for the protection, control and
monitoring functionalities specified.
c) The Human Machine Interface (HMI) shall be located on the compartment door and all control
facilities shall be accessible from the front of the panel.
d) The compartment door shall be of swing frame design.
e) The low voltage compartment design shall allow for control cables to be added either from the top or
the bottom.
f) Slots or holes used to channel control cables into the low voltage compartment shall be sealed off to
prevent debris from adjacent compartments during an arc flash incident.
3.2.4.3 Power Cable Compartment
a) The power cable terminations and current transformers shall be accessible from the power cable
compartment.
b) The panel shall be designed such that it allows for disconnection of power cables, removal and
replacement of current transformers with the main busbars energised. In other words, the panel
shall be designed such that arc flash occurring in one compartment does not propagate to other
compartments.
c) The power cable compartment shall comply with the SANS 876 and shall provide for both single
core or three core cables type 2 (shrouded) terminations, unless otherwise specified.
d) Special procedures shall be required to access the power cable compartment in accordance with
ORHVS in 240-114967625.
3.2.4.4 Main Busbar Compartment
a) The main busbar compartment shall house the busbars and the busbar support structures.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
b) Special procedures shall be required to access the main busbar compartment in accordance with
ORHVS in 240-114967625.
3.2.4.5 Circuit-breaker Compartment
a) A dedicated compartment shall be provided to house the circuit-breaker.
b) The compartment of the withdrawable device shall be an operator-accessible compartment as per
interlocking requirements.
c) The switchgear panels design shall be the mid-mount/ floor-mount withdrawable type, that shall
ensure to provide:
plates within the switchgear panel, and
switchgear panels shall be achieved by ensuring the correct floor level alignment for trolleys or
circuit-breaker floor level wheel movement during the switch room design. This floor level alignment
requires the switchgear room floor design to consider where applicable:
cable trench mounted base frame alignment to the onsite casted switchgear room floor level,
concrete floor levels where switchgear panels are mounted directly on top of the floor, and
steel base raised floor levels.
confirm the status and physical correct position of the cassette mounted circuit-breaker on the panel
mounted rails inside the switchgear panels for; the ready to withdrawal position, the inserted and
ready to rack in position and the in-service position.
d) A hole shall be provided on the circuit-breaker door aligning with the OFF pushbutton of the circuit-
breaker. This is to allow circuit-breaker to be tripped directly during an emergency. The special tool
shall be provided to trip the circuit-breaker or an attached mechanism on the door shall be provided
for the tripping function of the circuit-breaker.
e) The ON pushbutton of the circuit-breaker shall be blanked off to prevent the circuit-breaker from
being closed directly. The circuit-breaker shall be closed via the IED at bay level or via the
Scada/dcs.
3.2.4.6 Busbar Earthing Device Compartment
a) The busbar earthing device compartment shall be a special-accessible compartment and requires
that the switchboard and all incoming and outgoing supplies to be isolated and tools shall be
required to open this compartment. The isolations shall comply with requirements of ORHVS in 240-
114967625 and Generation Plant Safety Regulations 240-150642762.
b) The busbar earthing device compartment shall be on the same panel as the VT compartment.
c) The busbar earthing device shall be operated from the front and the outside of the panel.
d) The busbar earthing device shall be of the fixed type. The use of a withdrawable device shall be
subject to Eskom acceptance.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.2.4.7 VT Compartment
a) The compartment of the VT device shall be a separate panel with an operator-accessible
compartment as per interlocking requirements to prevent access to the VT while racked in.
b) The VT shall be of the withdrawable type.
3.2.5 Service Continuity Classification
The loss of service continuity category shall be LSC2B in accordance with SANS 62271-200.
3.2.6 Partition Class and Shutters
a) Partition class PM classification as defined in SANS 62271-200 shall be required for shutters to the
breaker compartment when breaker is withdrawn to the disconnected, test, earthed or removed
position.
b) Automatically-operated shutters shall be provided so that on racking out of the circuit-breaker, these
shutters cover the busbar and cable connection points inside the spouts automatically to prevent
inadvertent contact with live busbars and cables.
c) Orifice shutter operation shall be positively driven in both directions. Solely gravity operated shutters
shall not be accepted.
d) Orifice shutters shall be automatically operated by the movement of the withdrawable part.
e) Spout shutters shall be arranged to operate independently for the busbar spout shutters and cable
connection spout shutters. These shutters shall be capable of being padlocked in the open and
closed position. Shutters shall operate without lubrication and shall be constructed in such a
manner as to ensure fail-safe operation.
f) Shutter endurance and reliability shall be proven by type testing to the number of operations as
specified.
g) Busbar spout shutters shall be coloured red and labelled with the word “BUSBAR” in black letters at
least 50 mm high.
h) Cable spout shutters shall be coloured yellow and labelled with the word “CABLE” in black letters at
least 50 mm high.
i) In case of bus-section circuit-breakers of switchboards joined by busbars both shutters shall be
labelled “BUSBAR”.
3.2.7 Cooling
a) The use of natural cooling on functional units is preferred over forced cooling.
b) Where forced cooling forms part of the standard design and type testing, the design shall be in
compliance with the following requirements:
c) No tripping of the circuit-breaker shall be allowed if the fan fails.
d) Monitoring of the fans shall be done using fan failure indications and alarms.
e) The cooling fan motor assembly shall be readily available in South Africa.
f) Low speed high volume fans shall be used.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.2.8 Degree of Protection
a) The required minimum degree of protection shall be in accordance with SANS 60529:
IPXXB for live parts (inside LV compartment), and
IP3X for cable boxes.
b) The degrees of protection of the switchboard offered shall be IP4X.
3.2.9 Panel Fasteners, Doors and Covers
a) Fasteners used in the construction of the functional unit shall not deviate from those used in the type
tested panels.
b) If the panel fastener is also the locking mechanism, provision shall be made for a padlock with
dimensions as specified in Figure 1.
c) Where the design allows for lift-off covers for the cable compartment, the cover shall be
mechanically interlocked with the cable earthing device. The cover shall only be removed if the
cable earth switch is applied.
d) All compartment doors housing a circuit-breaker or Busbar VT shall be fitted with a front window, for
the purpose of indicating the mechanical status of the component within, that was part of the type
testing for internal arc compliance.
e) Cable compartments shall be fitted with a bolted cover or doors. Interlocks are mandatory when
accessing the cable VT.
f) Cable compartment doors shall be tool-based accessible and lockable.
g) Where doors are provided for empty compartments, the doors shall be pad-lockable with a padlock
as shown in Figure 1.
Figure 1: Eskom standard padlock.
3.2.9.1 Padlocking facilities
a) Facilities shall be provided to padlock the following:
all orifice shutters individually in the closed position;
the circuit-breaker in each of the service and test/disconnected positions;
the integral earthing switches in both the open and earthing positions; and
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
button.
b) All padlock facility positions shall be labelled.
c) All padlocking facilities shall be suitable for padlocks that have a shackle diameter of 8 mm, as
shown in Figure 1.
3.2.10 Corrosion Protection
a) Steelwork shall be corrosion protected in accordance with the standard 240-75655504. Where
corrosion protection is not in accordance with the Eskom standard, the tenderer shall provide proof
that the method of corrosion protection applied is equal or better than the stipulated requirements in
240-75655504.
b) The colour of the final coating shall be in accordance with SANS 1091.
3.2.11 Labels and Colour Coding
3.2.11.1 General
a) All local paint colours shall be standard colours in accordance with SANS 1091. Imported colours
(RAL) shall match local colours.
b) All labels shall be in accordance with labelling standards found in 240-71432150 and 0.00-10343
Sheets 1 and 2.
c) Labels shall be inscribed in English. The content of the label shall be provided by Eskom following
the relevant plant codification standard.
3.2.11.2 Colour Coding of Switchboards
All switchgear panels need to be painted as per the system voltage categories in Table 1 below. For
voltage categories not covered in Table 1, special instructions will be provided for each project by
Eskom. The painting of panels shall include all front covers, side covers and back covers.
Table 1: Colour Coding of Switchboards.
Voltage (kV) Colour
15 Local H09
Imported RAL 6028
11 Local H09
Imported RAL 6028
6.6 Local B32
Imported RAL 2000
3.3 Local B32
Imported RAL 2000
3.2.11.3 Warning Labels for Internal Arc Classified Board
a) In cases where the design of the functional unit is such that the blow out is to the top of the
functional units in order as to fulfil the IAC requirements, the switchboard shall be labelled to provide
warning messages to people working on the panels.
b) The following is the prescription for the warning labels required:
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
c) DO NOT CLIMB ON TOP OF THE SWITCHGEAR WHEN ENERGISED. The labels shall be
installed at the rear and the sides of the switchboard. The number of labels on the rear shall depend
on the length of the board.
d) DO NOT STEP ON THE PRESSURE RELIEF FLAPS. The labels shall be installed at locations
clearly visible and in close vicinity to the flaps.
e) The warning labels shall be of red lettering on a white background.
3.2.12 Busbars and Connections
a) The main busbars compartment and connections inside the busbar compartment shall be air
insulated and the clearances shall not compromise the specified voltage withstand levels. The
busbars shall be supplied as per the type tested arrangement, including any additional insulation
shrouding or tubes that were used.
b) Cables are not allowed to be used for busbars or busbar connections inside the circuit-breaker,
busbar voltage transformer and busbar compartments.
c) All busbars shall be marked per panel in such a manner that they shall be easily identifiable as to
the phase or pole they are connected to when covers are removed. It is recommended to use heat
shrink tube for marking however, the material used for marking the busbars is subject to Eskom
acceptance.
d) Busbar connections shall be made with at least two bolts and the overlap is sufficient to ensure
ample mechanical strength and joint conductivity. The busbar connections shall match those of a
type tested panel. Silver tinted or tinted copper joint interfaces are preferred.
3.2.13 Spouts, Bushings and Insulators
a) Moulded type bushings and spouts shall be used as the connection between circuit-breakers and
busbars.
b) All bushings and insulators shall have permissible levels of partial discharge in accordance with
SANS 62271-200.
3.2.14 Insulating Materials
a) The insulation material shall be identical to the material used during voltage withstand and
temperature rise type testing.
b) Insulating materials may be used in areas where the insulation level criteria cannot be met with air
as an insulating medium.
c) Where insulation on busbars is required, it shall be of the heat shrink type with non-static
characteristics.
d) Where insulating barriers are required, the material used shall be of a non-static type.
3.2.15 Auxiliary Circuit Wiring and Identification
a) The wiring, terminals, lugs, identification and installation shall be in accordance with Drawing
0.00/10341.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
b) All control wiring shall be of a neat appearance and suitably braced, placed in wire trunks, clipped
and/or laced to prevent vibration and not to be deformed under through fault conditions.
Connections to equipment on swing doors shall be arranged so as to give a twisting motion and not
a bending motion to the conductor.
c) For identification all leads shall be marked at both ends with an approved type of marking device in
accordance with the schematic diagram. Interlocking type ferrules with permanent black letters
impressed on a white or yellow background are preferred. The number ferrule shall not fall off when
disconnecting the wire. Ferrules shall read in a consistent manner in both vertical and horizontal
planes (see Drawing 0.00/10341 Sheets 3 and 4).
d) Control wire sheaths shall be coloured as follows:
AC circuits: Black
DC circuits: Grey
Earthing: Green and yellow
CT and VT wiring shall be coloured as per the phase - red, white, blue and black (neutral).
CT wiring: Wiring between the current transformer and the low voltage compartment
terminals shall be coloured as per the phases – red, white, blue and black (neutral) with
wire numbers in accordance in Drawing 0.00/10341 Sheets 4.
VT wiring: Wiring between the voltage transformer and the first fuse shall be coloured as per
the phases. After the first fuse the AC wiring shall be all black with wire numbers in
accordance in Drawing 0.00/10341 Sheets 4.
e) Control wiring shall be terminated with pre-insulated compression type lugs. Each terminal strip
mounting rail shall be provided with not less than 10% spare length with a minimum of 50 mm. Not
more than two conductors shall be connected to any side of a terminal, so that the size of all
terminals is suitable for the termination of two cables/wires of 4 mm2 each.
f) For top cable entry into the low voltage compartment, gland plates for control cables shall be
provided . An arrangement of terminals in the low voltage compartment allow for easy termination of
all cables brought in. The number of control terminals shall be in accordance with the control
drawings for that specific panel. Allowance shall be made for any possible inter-panel or looped bus
wiring, from one low voltage compartment to the next low voltage compartment.
g) All external control cables shall be brought into the low voltage compartment, within a separate
channel from the power cable compartment.
3.2.16 Power Cable Entry and Termination
3.2.16.1 Power Cable Termination
a) The power cable compartment shall be adequately sized to allow for the termination in air.
Allowance shall be made inside the cable compartment to install the termination kits for either PILC
or XLPE MV cables of the same voltage rating as the panel, unless otherwise specified.
b) The distance between cable termination points and adjacent structures within the compartment shall
be in accordance with SANS 876.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
c) Provision shall be made to allow for the termination of multiple cables per phase. It is required to
always provide one termination flag per cable to be terminated. The number of cables shall be
provided in the MV Switchgear Schedule 240-77300784.
3.2.16.2 Gland Plates
a) Gland plates shall be of pre-galvanised or aluminium sheets and the switchgear manufacturer shall
provide a means to ensure good metallic contact between the gland plate and the body of the panel.
The number of cables shall be provided in the MV Switchgear Schedule 240-77300784
b) There shall be an earth path continuity for the armouring through gland, gland plate to panel and
earth bar.
c) For single-core cables, a non-ferrous or split-stainless steel gland plate shall be used to eliminate
eddy currents.
3.2.16.3 Cable Entry Arrangements
The minimum requirements shall be as per the SANS 876: Distance from terminal centre line to gland
plate or cable clamp. Any through wall plates or gland plates mounted between the bushing centre line
and cable clamps shall be a minimum distance of 800 mm from the bushing centre line to the through
wall plate or gland plate to allow for standard Eskom three core cable terminations, unless otherwise
specified. For single-core cables the minimum distance shall be 600mm from terminal centre line to
gland plate or cable clamp.
3.2.16.4 Vermin and Fire Proofing of Cable Compartment and LV Compartment
a) All cable compartments shall be designed to be sealed off with a 2 hour fire retardant material of at
least 50 mm thick at floor level, after the cables have been installed, to ensure that fire cannot
propagate from the basement/trench into the switchgear cable compartment.
b) For top entry of control cables into the LV compartment, all unused gland holes shall be sealed.
c) The space provided beneath the switchgear panel in the trench shall allow for the installation of fire
retardant material, to the extent that during an internal arc in the cable compartment there shall be
no pressure release or any smoke or heat to the front of the panel, the rear of the panel, into the
cable trench or tunnel or any adjacent compartments and functional units.
3.2.17 Earthing
a) Holes shall be provided for connecting the station earth to the switchboard earthing bar inside the
switchgear panels. The earthing bar shall not extend outside the last panel.
b) Provision shall be made for the earthing bar to be connected to the station earth mat at least at both
ends of the board and for boards exceeding 15 m in length shall be connected to the station earth in
at least three places.
c) For any earth bar, it is required to provide 25 mm wide earth bar with a suitable thickness calculated
to provide an equivalent fault current carrying capacity of at least 200 A/mm2. The impact of holes in
the earth bars shall also be considered to ensure the fault current rating equivalent cross section
required.
d) All doors and covers shall be earthed to ensure that the touch potential does not exceed the safe
values as specified in the OHS Act.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.2.18 Busbar Extension Dummy Panels
a) The busbar extension dummy panel shall be designed and constructed to ensure compliance to the
type tested switchgear panel design and arrangement.
b) Where Busbar extension dummy panels are installed the main busbars shall not be accessible.
3.3 Special consideration for internal arc proof design
a) Pressure relief flaps in a power compartment shall be designed such that the gasses are not
directed to any other compartment during an internal arc fault.
b) Each power compartment shall have dedicated exhaust channel inside the panel to the pressure
relief flaps.
c) Each compartment shall contain the arc without spreading it to other compartments.
d) Each functional unit (panel) shall contain the arc without spreading it to any other functional unit/s.
e) Due to the internal arc classification and for maintenance purposes, no VTs or earthing device shall
be installed within the pressure relief area on top of any functional unit.
f) On fault levels equal and above 25kA, all switchboards shall be equipped and type tested with
exhausting ducts to channel the hot gasses generated by internal arc fault to the outside of the
substation. All applicable type test reports and type test videos shall be provided during tender
evaluations.
g) On fault levels below 25kA, the design of switchboard may allow for venting to the inside of the
substation switchgear room subject to Eskom’s acceptance. In such a case, proof of type test
reports and type test videos shall be submitted for Eskom tender evaluations. During design phase
simulation reports, by calculation or other means, shall be submitted to declare that it is safe to vent
inside the substation(s).
h) Switchboard fitted with the exhaust duct shall not have common duct with the next switchboard. (i.e.
Switchboard A shall not have common ducts with Switchboard B even if they are connected by
bisection circuit-breakers.
i) For substations with soft ceilings and/or windows (glass), venting shall be directed to the outside of
the substation via the exhausting duct.
j) IAC requirements shall be upheld while working in the low voltage compartment. Hence, the
channels or conduits between the power compartments and the low voltage compartments should
be sealed accordingly and type tested with the LV compartment door removed.
3.4 Circuit-breakers
3.4.1 General
a) Circuit-breakers shall be in accordance with SANS 62271–100
b) Circuit-breakers are of the triple-pole withdrawal type with visible indication which is mechanically
interlocked with the circuit-breaker.
c) The arc-quenching medium and/or insulation are of the type tested as specified.
d) Withdrawable circuit-breakers are housed in a circuit-breaker compartment of the “behind close
door” design.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
e) The circuit-breaker operation under emergency operating conditions shall comply with the “behind
close door” design.
f) Total current interruption (break) time as defined in SANS 62271-100 shall not be greater than the
time duration specified, under all operating conditions.
g) Where circuit-breakers are used, the power connecting arms are fully insulated. Bare copper as
connecting arms are not acceptable.
h) Where bus-zone protection is required, the bus-section circuit-breaker design shall allow for the
installation of current transformers on each side of the bus-section circuit-breaker.
i) Where vacuum interrupters are used in the circuit-breaker design, only the type tested vacuum
interrupter design or product specific code as per the type test report designation shall be offered
during tender evaluation.
3.4.2 Inter-changeability
The circuit-breaker main and secondary circuit contacts shall be such that all circuit-breakers of the
same type, current rating and auxiliary configuration are interchangeable. However, it shall not be
possible to insert a circuit-breaker of lower rating into a circuit of a higher current rating.
3.4.3 Circuit-breaker mid-mount trolley/floor-mount connections
a) Where the control connections between the circuit-breaker mid-mount/floor-mount trolley and the
circuit-breaker compartment are made by means of flexible connections these shall be contained in
a flexible conduit.
b) If metallic conduit (between the control plug and circuit-breaker) is provided, this shall be covered by
an approved insulating material. A means shall be provided to retain the flexible connection out of
the path of the circuit-breaker when the mid-mount trolley/floor-mount is inserted into or removed
from the circuit-breaker compartment.
c) Where control connectors are of the multi-pin design the connecting pins and female studs shall be
of the removable design and secured into position.
3.4.4 Mechanisms and Closing Devices
a) Mechanisms as per SANS 62271-1, SANS 62271-100, SANS 62271-102 and SANS 62271-200
shall be provided.
b) All conventional circuit-breakers and actuator circuit-breakers electrically-operated closing devices
including mechanism charging motors shall be suitable for operation at any voltage between 85%
and 110% of nominal control voltage measured at the terminals of the device.
c) The circuit-breaker shall close correctly when an electrical closing pulse of 100 ms duration is
applied to the closing coil.
d) The total power drawn by the closing coil, excluding closing solenoids, shall not exceed 1200 VA per
circuit-breaker.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.4.5 Tripping Devices
a) All conventional circuit-breakers and actuator circuit-breakers electric tripping devices shall be of the
shunt type, suitable for operating at any voltage between 85% and 110% of the rated control voltage
measured at the device terminals.
b) Two normally-open auxiliary contacts in parallel shall be included per tripping circuit in series with
the trip coil.
c) Circuit-breakers design shall make provision for the installation of a second tripping coil as per the
voltage specified. This second trip coil shall form an integral part of the design of the circuit-breaker
complete with interlocking.
d) Circuit-breakers design shall make provision for the installation of an under voltage release coil as
per the voltage specified in MV Switchgear Schedule 240-77300784.
e) This under voltage release coil shall form an integral part of the design of the circuit-breaker
complete with interlocking.
f) Where a circuit-breaker is used for safety application, such as Boiler Protection Systems, it shall
meet the specified safety integrity level (SIL) requirements as a minimum. A confirmation that safety
requirement is met must be provided with tender submissions in the form of certification to SANS
61508 or SANS 61511 whichever applicable, datasheet of under voltage release coil, safety
application notes, etc.
3.4.6 Indicating Devices
a) A positive driven mechanical indicating device to show whether the circuit-breaker is open or closed
shall be provided. The devices are labelled as follows:
Circuit-breaker close: ON or I – white lettering on a red background
Circuit-breaker open (Trip): OFF or O – white lettering on green background
Note: The Eskom colour coding convention for trip/close actuators is opposite to that specified in IEC 60073 (i.e.
IEC requires trip red and close green).
b) Lettering size shall not be less than 10 mm. The method of securing the labels shall be as per the
requirements of this standard.
c) Where the circuit-breaker position is not visible from the front of the panel, a positive driven
mechanical indicator shall be provided to indicate whether the circuit-breaker is in the service or
disconnected position, or state the position of the integral-connected disconnector, whichever is
applicable.
d) All mechanical indicators shall be clearly visible from the front of the panel and are type tested for
the number of operations of the operating device to prove the reliability of the indicating mechanism.
3.4.7 Auxiliary Contacts
a) Auxiliary contacts shall be readily accessible and the preference shall be for contacts with a
pronounced wiping action.
b) Sufficient auxiliary contacts shall be provided as per the schematic drawings and the requirements
for spare contacts.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
c) The spare contacts shall be easily replaceable with normally open or normally closed contacts and
shall be wired to the outgoing control terminals. Auxiliary contacts positively follow the action of the
main contacts.
d) Suitable arrangements shall be made to ensure that circuit-breaker auxiliary contacts only signal the
change of state when the circuit-breaker is in the service and disconnected position.
e) Where insufficient contacts are available, a continuously rated slave relay shall be provided but is
used for indication circuits only.
3.4.8 Control Connector
a) Control connectors shall be of the multi-pin design with removable pins for male and female
connectors.
b) Connectors shall be of on load design.
c) Control connectors shall have the facility to be coded to differentiate between different circuit-
breaker types, ratings and functions or protection schemes for the same rated circuit-breakers.
3.4.9 Insulation Level
a) Internal insulation and clearances in air shall comply with the requirements for live conductors in
accordance with SANS 876; unless otherwise proven by dielectric and partial discharge type testing
to the required insulation levels.
Note: In general, this type of air-insulated switchgear is designed for either type 1 (bare) or type 2
(shrouded/covered) live conductor arrangements in accordance with SANS 876.
b) The insulation level of all circuit-breakers, busbars, busbar connections and any other related
components shall be in accordance with the values specified in MV Switchgear Schedule 240-
c) The use of insulation material barriers for phase segregation to increase the insulation level shall be
not acceptable if not type tested.
d) No insulation material shall be used that may lead to material ageing and degradation for the
insulation levels specified over time, or may lead to partial discharge of the panel due to ageing or
possible dust collection.
e) Where insulating materials are part of the integral design of the switchgear, the life expectancy shall
be guaranteed by means of testing where applicable and material data sheets for the prescribed
installation conditions.
3.5 Disconnectors
a) Disconnector shall be in accordance with SANS 62271–102.
b) All disconnectors shall be of the air-break, triple-pole, gang-operated type.
c) Use of fully functional circuit-breaker switchgear panel in the racked out (disconnected) position to
fulfil the on-load isolation purpose is allowed.
d) The disconnector position indicator shall be visible from the front of the panel. A positive driven
mechanical indicating device to show whether the disconnector is open or closed shall be provided.
The requirements in Clause 3.4.6 also apply to disconnector.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
e) All disconnectors shall be operated by means of a handle and from the front with the panel door
closed.
f) Provision shall be made for a mechanism that enables padlocking in both the “ON” and “OFF”
positions to inhibit operation of the disconnector.
g) The closing operation of the disconnector shall require minimal application of speed and force on the
operating handle.
3.6 Earthing devices
3.6.1 General
a) Earthing devices shall be in accordance with SANS 62271–102.
b) The switchgear design shall include busbar and cable earthing devices as an integral part of the
associated functional unit.
c) All earthing devices shall be operated from the front and outside of the panel.
d) Earthing switches shall be fitted with motorising mechanism to allow for applying of earth remotely.
e) Provision shall be made for a mechanism that enables padlocking in both the “ON” and “OFF”
positions to inhibit operation of the earthing devices.
f) Interlocks shall be provided in accordance with SANS 62271-200.
g) Earthing of cables or busbars via the enclosure and supporting structures shall not be acceptable.
h) The earthing device position indicator shall be visible from the front of the panel. A positive driven
mechanical indicating device to show whether the earthing device is open or closed shall be
provided. The requirements in Clause 3.4.6 also apply to earthing devices.
3.6.2 Busbar Earthing Devices
a) Busbar earthing devices shall be provided for the main busbars.
b) Busbar earthing devices shall be used to provide connection between all three phases of the main
busbars and main earth bar through isolating bushings where applicable.
c) The busbar earthing device may only be mounted in the busbar compartment.
3.6.3 Cable Earthing Device
a) Cable earthing switches shall be provided for all incoming and feeder circuit panels.
b) Interlocking shall be required for the cable earthing device to be applied before the cable
compartment door or cover can be opened.
c) Interlocking shall also be provided for utilizing the cable live indication system (VDS) to prevent
closing of the earthing switch onto live cables.
d) Cable earthing devices shall be connected between all three phases of the cable terminals and main
earth bar.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.7 Special requirements for generator circuit-breaker
3.7.1 General
a) This standard includes requirements for 10 to 100MVA generator circuit-breakers and it excludes
requirements for generator circuit-breakers that are rated 100 MVA and above. These generator
circuit-breakers are housed in an AC metal enclosed switchgear and controlgear.
b) Metal enclosed switchgear and controlgear used for power generation and export system shall
comply with all the requirements of this Eskom MV Switchgear standard with the following
exceptions;
above the anticipated earth fault level.
of the functional unit/panel and shall be rated above the anticipated fault level.
c) The circuit-breaker duty cycle of “CO – 30 minutes – CO” is applicable only in the case of the rated
short-circuit current interruption duty. For non-fault interruption, the duty of “CO - 3 minutes – CO” is
applicable.
3.8 Accessories
3.8.1 Current Transformers
a) Current transformers shall comply with SANS 61869 part 1 and 2.
b) Current transformers shall be installed inside the associated functional unit such that they are easily
accessible and removable.
c) The short-time withstand current rating of current transformers shall not be less than that of the
associated circuit-breaker.
d) Secondary windings of current transformers shall be earthed at one point only. Each group of
current transformers (i.e. protection, metering etc.) shall be earthed to the earth bar using solid wire.
e) All current transformers shall be of air-cooled design and the cooling shall be through natural flow of
air.
f) Additional rating plates made of a durable material shall be provided with markings as per
SANS 61869-2. The information on the additional rating plates shall be duplicated from that
appearing on each current transformer and shall be located within the low voltage compartment in a
position giving easy visibility.
g) The phase colour with which each current transformer is associated shall appear on the CT name
plate that is mounted inside the LV compartment door.
3.8.2 Voltage Transformer
a) VTs shall comply with SANS 61869 part 1 and 3.
b) VTs shall be of the resin encapsulated type and air-cooled design. The cooling shall be through
natural flow of air.
c) VTs shall be of the single-phase design, where applicable for motor starter panels.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
d) VTs s shall be of the withdrawable type.
e) The primary side of busbar connected VT panels shall be connected to the busbars via adequately
rated HRC fuses. It shall not be possible to gain access to these HRC fuses with the VT in the
service position.
f) The busbar connected VT shall be of the plug-in type and arranged such that it can be isolated and
removed without affecting the associated circuits.
g) When VTs are withdrawn, the spouts shall be closable by means of automatic shutters. The
shutters shall have padlocking facilities.
h) Provision shall be made to enable locking of the busbar connected VT in the “service” position.
i) All VTs shall be star primary and star secondary connected. The VT shall be earthed at both the
primary and secondary star points.
j) The circuit on the secondary side of the VT shall be protected with the use of either fuses or mcb’s.
The protection devices shall be mounted on the VT in order to include the wiring from the VT to the
LV compartment in the protected circuit.
k) The secondary fuses of the cable VT shall be easily accessible without any danger of having to work
in a live chamber. No fuses or mcb’s shall be fitted in a phase-circuit that is connected to earth.
l) The VT shall be connected to the earth bar by means of solid wires.
3.8.3 Indicating and Measurement Instruments
a) All instruments shall be of the flush-mounting industrial type in accordance with IEC 60051 for
indicating instruments of Class 1.5 category.
b) Transducers shall conform to IEC 60688.
3.8.4 Cable and Busbar Live Indicators
An “integrated” voltage detection system (VDS) with fixed voltage indicators and test points in
accordance with SANS 61243-5 shall be provided for cable live indication on each incomer and feeder
panels, and busbar live indication on each bus section and/or bus coupler panel.
3.8.5 Wiring and Cable Lugs
a) Control wiring lugs and their application with different types of terminals shall be in accordance with
Drawing 0.00-10341 Sheets 1 to 4.
b) Crimping on of power lugs shall be in accordance with SANS 61238-1. Crimping tools shall be re-
calibrated according to their manufacturer’s standards.
3.8.6 Nameplates and Labels
a) Each switchgear panel shall be labelled in accordance with the nameplate requirement of SANS
62271-200. In addition to the requirements of SANS 62271-200.
b) Each circuit-breaker shall be separately labelled in accordance with the nameplate requirement of
SANS 62271-100. The following additional information shall be provided for the circuit-breaker
operating mechanism:
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
Manufacturer OEM name,
The relevant SANS reference number,
Trip-coil voltage, current, d.c. resistance (at 20 0C),
Close-coil voltage, current, d.c. resistance (at 20 0C), and
Motor voltage and current (starting peak current and nominal running current).
c) Each switchboard labels shall be provided with a labels which complies with the standards found in
240-71432150 and 0.00-10343 Sheets 1 and 2.
d) Main, circuit description, components and operating labels shall be in accordance with 240-
3.9 Switchgear interlocking systems
a) All interlocks shall be in accordance with SANS 62271(relevant parts).
b) Mandatory mechanical interlocks shall be provided for the withdrawable circuit-breakers to ensure
that:
circuit-breaker main contacts are fully open.
position.
be removed/opened when the circuit-breaker is in the service position and during racking of the
circuit-breaker.
position and cable VDS indication is dead.
supply switched on to enable the circuit-breaker to be placed in the service position.
Circuit-breakers cannot be closed unless the cable earth switch is in the open position.
Busbar earthing is only possible when all busbar supply circuit-breakers and circuit-breakers of
feeder panels are in the disconnected position.
open, the circuit-breaker cannot be moved from the disconnected position to the service position.
earth switch applied).
c) The requirements for non-mechanical interlocks shall conform to required operating philosophy
presented by Eskom, defined schematic drawings and SANS 62271-200.
d) Where blocking magnets are used as part of the system interlocking, the rating of the blocking
magnets shall be continuously rated and shall comply with the control voltage rating and variations.
e) Where electrical system interlocking is preferred, the details shall be specified by Eskom.
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.10 Testing
3.10.1 Type Test
a) The type tests shall be carried out on all types of functional units in accordance with SANS 62271-
b) Where extension of validity of type tests is performed, SANS 62271-307 guide shall be used to
perform interpolation of characteristics covering various designs and rating aspects.
c) The electrical components affecting the performance of the functional unit shall be type tested in
accordance with the relevant parts of SANS 62271 and other applicable standards.
d) CTs shall be type tested in accordance with SANS 61869 part 1 and 2.
e) VTs shall be type tested in accordance with SANS 61869 part 1 and 3.
f) Cable live indicators shall be type tested in accordance with SANS 61243-5.
g) The indoor switchgear panels (functional units) shall be type tested in accordance with SANS
62271-200, under the authority of a laboratory accredited by a full member (MRA signatory) of ILAC
(International Laboratory Accreditation Cooperation). Type test authorities for switchgear and
controlgear shall be accredited in accordance with ISO 17025.
h) All type tests and extension of validity of type tests shall be verified and accepted by Eskom before
manufacturing can start.
3.10.2 Routine Tests
a) Routine tests shall be performed on each of the functional units and associated components.
b) Switchgear and controlgear shall be routine tested in accordance with the relevant parts of SANS
c) CTs shall be tested in accordance with SANS 61869-2.
d) VTs shall be tested in accordance with SANS 61869-3.
e) All the other components forming part of the functional unit shall be tested in accordance with the
applicable standards to prove functionality.
f) For prototype panels, full range of the required routine tests shall be conducted in accordance with
SANS 62271 (all relevant parts) and witnessed by Eskom.
3.10.3 Special Test – Open door LV compartment
a) The LV compartment design shall ensure that no internal arc flashover or debris within the circuit
breaker, busbar or cable compartments shall vent into the LV compartment i.e. the internal arc
classification achieved for the switchgear panels shall be of such a nature that opening the LV
compartment door does not compromise the type tested IAC. Sufficient proof shall be submitted
from the already performed IAC type tests performed to proof that. If no proof can be submitted
during tendering, the re-type testing of the complete switchgear panel with LV compartment door
open for internal arc classification shall be required prior to contract conclusion.
If no proof can be submitted during tendering, the re-type testing of the complete switchgear panel
with LV compartment door open for internal arc classification. The following are the requirements;
Controlled disclosure
When downloaded from the EDMS, this document is uncontrolled and the responsibility rests with the user to ensure it is in line
with the authorised version on the system.
Quality Management
Source: 240-56227573 Air-Insulated Withdrawable AC Metal-Enclosed Switchgear Controlgear for 1kV to 52kV.pdfwith the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.2.16.4 Vermin and Fire Proofing of Cable Compartment and LV Compartment ..................................... 21
3.2.17 Earthing ................................................................................................................................................. 21
3.2.18 Busbar Extension Dummy Panels ......................................................................................................... 22
3.3 Special consideration for internal arc proof design ......................................................... 22
3.4 Circuit-breakers ..................................................................................................................................... 22
3.4.1 General .................................................................................................................................................... 22
3.4.2 Inter-changeability ................................................................................................................................... 23
3.4.3 Circuit-breaker mid-mount trolley/floor-mount connections .................................................................... 23
3.4.4 Mechanisms and Closing Devices .......................................................................................................... 23
3.4.5 Tripping Devices ...................................................................................................................................... 24
3.4.6 Indicating Devices ................................................................................................................................... 24
3.4.7 Auxiliary Contacts .................................................................................................................................... 24
3.4.8 Control Connector ................................................................................................................................... 25
3.4.9 Insulation Level ....................................................................................................................................... 25
3.5 Disconnectors ......................................................................................................................................... 25
3.6 Earthing devices ..................................................................................................................................... 26
3.6.1 General .................................................................................................................................................... 26
3.6.2 Busbar Earthing Devices ......................................................................................................................... 26
3.6.3 Cable Earthing Device ............................................................................................................................. 26
3.7 Special requirements for generator circuit-breaker ........................................................ 27
3.7.1 General .................................................................................................................................................... 27
3.8 Accessories ............................................................................................................................................... 27
3.8.1 Current Transformers .............................................................................................................................. 27
3.8.2 Voltage Transformer ................................................................................................................................ 27
3.8.3 Indicating and Measurement Instruments ............................................................................................... 28
3.8.4 Cable and Busbar Live Indicators ........................................................................................................... 28
3.8.5 Wiring and Cable Lugs ............................................................................................................................ 28
3.8.6 Nameplates and Labels ........................................................................................................................... 28
3.9 Switchgear interlocking systems .................................................................................................. 29
3.10 Testing ....................................................................................................................................................... 30
3.10.1 Type Test ............................................................................................................................................... 30
3.10.2 Routine Tests ........................................................................................................................................ 30
3.10.3 Special Test – Open door LV compartment .......................................................................................... 30
3.11 Maintenance and operation ............................................................................................................. 31
3.11.1 Maintenance and Operating Tools ........................................................................................................ 31
3.11.2 Maintenance and Operating Instructions .............................................................................................. 31
3.12 Training ..................................................................................................................................................... 31
3.13 Documentation ....................................................................................................................................... 31
3.13.1 Language............................................................................................................................................... 31
3.13.2 Type Test Reports ................................................................................................................................. 31
3.13.3 Manuals and Drawings .......................................................................................................................... 32
3.14 Packaging, transportation and handling ................................................................................. 32
3.15 Spares ........................................................................................................................................................ 33
3.15.1 Availability of spares .............................................................................................................................. 33
3.15.2 Identification of spares .......................................................................................................................... 34
Authorisation .................................................................................................................................................. 34
Revisions ............................................................................................................................................................ 35
Development team ......................................................................................................................................... 35
Acknowledgements ...................................................................................................................................... 35
Annex 1: technical schedule c- type testing requirements .......................................................... 36
Annex 2: technical a & b schedule for generation air-insulated withdrawable ac
Metal-enclosed switchgear and controlgear for rated voltages above 1kv up
To and including 52kv .................................................................................................................................. 40
Annex 3: mv switchgear schedule .............................................................................................................. 60
[37] SANS 1195 Busbars.
[38] SANS 1411-1 Materials of Insulated Electric Cables and Flexible Cords: Part 1: Conductors.
[39] SANS 61213 Mechanical Cable Glands.
[40] SANS 60060 High-Voltage Test Techniques.
[41] SANS 60269 Low-Voltage Fuses.
[42] SANS 60947 Low Voltage Switchgear and Controlgear. All parts
[43] SANS 61238-1 Compression and Mechanical Connections for Power Cables for Rated Voltages
up to 30 kV(Um=36kV) Part 1: Test methods and requirements.
[44] IEC 60051 Direct-Acting Analogue Electrical Measuring Instruments and their Accessories.
[45] IEC 60688 Electrical Measuring Transducers for Converting AC and DC Electrical Quantities
to Analogue or Digital Signals.
[46] IEC/IEEE 62271-37-013 High-Voltage Switchgear and Controlgear – Part 37-013: Alternative –
current generator circuit-breakers.
[47] IEEE Std C37.013a Standard for AC High Voltage Generator Circuit-breakers Rated on a
Symmetrical Current Basis – Amendment 1: Supplement for Use with Generator
Rated 10-100 MVA.
[48] ISO 17025 General Requirements for the Competence of Testing and Calibration Laboratories
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
[49] ISO 9001 Quality Management Systems.
[50] CDA Publication 22 Copper Development Association (CDA), Publication 22, Copper for
busbars.
[51] IEC 60038 Standard Voltages.
[52] IEC 60518 Dimensional standardisation of terminals for high-voltage switchgear and
controlgear.
[53] EPRI 10003471 Electrical Connector Guideline.
2.2.2 Informative
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.2.8 Degree of Protection
a) The required minimum degree of protection shall be in accordance with SANS 60529:
IPXXB for live parts (inside LV compartment), and
IP3X for cable boxes.
b) The degrees of protection of the switchboard offered shall be IP4X.
3.2.9 Panel Fasteners, Doors and Covers
a) Fasteners used in the construction of the functional unit shall not deviate from those used in the type
tested panels.
b) If the panel fastener is also the locking mechanism, provision shall be made for a padlock with
dimensions as specified in Figure 1.
c) Where the design allows for lift-off covers for the cable compartment, the cover shall be
mechanically interlocked with the cable earthing device. The cover shall only be removed if the
cable earth switch is applied.
d) All compartment doors housing a circuit-breaker or Busbar VT shall be fitted with a front window, for
the purpose of indicating the mechanical status of the component within, that was part of the type
testing for internal arc compliance.
e) Cable compartments shall be fitted with a bolted cover or doors. Interlocks are mandatory when
accessing the cable VT.
f) Cable compartment doors shall be tool-based accessible and lockable.
g) Where doors are provided for empty compartments, the doors shall be pad-lockable with a padlock
as shown in Figure 1.
Figure 1: Eskom standard padlock.
3.2.9.1 Padlocking facilities
a) Facilities shall be provided to padlock the following:
all orifice shutters individually in the closed position;
the circuit-breaker in each of the service and test/disconnected positions;
the integral earthing switches in both the open and earthing positions; and
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
c) DO NOT CLIMB ON TOP OF THE SWITCHGEAR WHEN ENERGISED. The labels shall be
installed at the rear and the sides of the switchboard. The number of labels on the rear shall depend
on the length of the board.
d) DO NOT STEP ON THE PRESSURE RELIEF FLAPS. The labels shall be installed at locations
clearly visible and in close vicinity to the flaps.
e) The warning labels shall be of red lettering on a white background.
3.2.12 Busbars and Connections
a) The main busbars compartment and connections inside the busbar compartment shall be air
insulated and the clearances shall not compromise the specified voltage withstand levels. The
busbars shall be supplied as per the type tested arrangement, including any additional insulation
shrouding or tubes that were used.
b) Cables are not allowed to be used for busbars or busbar connections inside the circuit-breaker,
busbar voltage transformer and busbar compartments.
c) All busbars shall be marked per panel in such a manner that they shall be easily identifiable as to
the phase or pole they are connected to when covers are removed. It is recommended to use heat
shrink tube for marking however, the material used for marking the busbars is subject to Eskom
acceptance.
d) Busbar connections shall be made with at least two bolts and the overlap is sufficient to ensure
ample mechanical strength and joint conductivity. The busbar connections shall match those of a
type tested panel. Silver tinted or tinted copper joint interfaces are preferred.
3.2.13 Spouts, Bushings and Insulators
a) Moulded type bushings and spouts shall be used as the connection between circuit-breakers and
busbars.
b) All bushings and insulators shall have permissible levels of partial discharge in accordance with
SANS 62271-200.
3.2.14 Insulating Materials
a) The insulation material shall be identical to the material used during voltage withstand and
temperature rise type testing.
b) Insulating materials may be used in areas where the insulation level criteria cannot be met with air
as an insulating medium.
c) Where insulation on busbars is required, it shall be of the heat shrink type with non-static
characteristics.
d) Where insulating barriers are required, the material used shall be of a non-static type.
3.2.15 Auxiliary Circuit Wiring and Identification
a) The wiring, terminals, lugs, identification and installation shall be in accordance with Drawing
0.00/10341.
with the authorised version on the system.
Generation Air-Insulated Withdrawable AC Metal-Enclosed Unique Identifier: 240-56227573
Switchgear and Controlgear for Rated Voltages above 1kV up Revision: 2
to and including 52kV Standard Page:
3.10 Testing
3.10.1 Type Test
a) The type tests shall be carried out on all types of functional units in accordance with SANS 62271-
b) Where extension of validity of type tests is performed, SANS 62271-307 guide shall be used to
perform interpolation of characteristics covering various designs and rating aspects.
c) The electrical components affecting the performance of the functional unit shall be type tested in
accordance with the relevant parts of SANS 62271 and other applicable standards.
d) CTs shall be type tested in accordance with SANS 61869 part 1 and 2.
e) VTs shall be type tested in accordance with SANS 61869 part 1 and 3.
f) Cable live indicators shall be type tested in accordance with SANS 61243-5.
g) The indoor switchgear panels (functional units) shall be type tested in accordance with SANS
62271-200, under the authority of a laboratory accredited by a full member (MRA signatory) of ILAC
(International Laboratory Accreditation Cooperation). Type test authorities for switchgear and
controlgear shall be accredited in accordance with ISO 17025.
h) All type tests and extension of validity of type tests shall be verified and accepted by Eskom before
manufacturing can start.
3.10.2 Routine Tests
a) Routine tests shall be performed on each of the functional units and associated components.
b) Switchgear and controlgear shall be routine tested in accordance with the relevant parts of SANS
c) CTs shall be tested in accordance with SANS 61869-2.
d) VTs shall be tested in accordance with SANS 61869-3.
e) All the other components forming part of the functional unit shall be tested in accordance with the
applicable standards to prove functionality.
f) For prototype panels, full range of the required routine tests shall be conducted in accordance with
SANS 62271 (all relevant parts) and witnessed by Eskom.
3.10.3 Special Test – Open door LV compartment
a) The LV compartment design shall ensure that no internal arc flashover or debris within the circuit
breaker, busbar or cable compartments shall vent into the LV compartment i.e. the internal arc
classification achieved for the switchgear panels shall be of such a nature that opening the LV
compartment door does not compromise the type tested IAC. Sufficient proof shall be submitted
from the already performed IAC type tests performed to proof that. If no proof can be submitted
during tendering, the re-type testing of the complete switchgear panel with LV compartment door
open for internal arc classification shall be required prior to contract conclusion.
Section
Source: 240-56227573 Air-Insulated Withdrawable AC Metal-Enclosed Switchgear Controlgear for 1kV to 52kV.pdfevaluations.
reports and type test videos shall be submitted for Eskom tender evaluations. During design phase
applicable standards to prove functionality.
[48] ISO 17025 General Requirements for the Competence of Testing and Calibration Laboratories
[49] ISO 9001 Quality Management Systems.
Description
Source: 240-56357424 MV and LV Switchgear Protection Standard (Rev 2.1).pdfThis is a technical standard document outlining the minimum protection requirements for medium voltage (MV) and low voltage (LV) plant at Eskom power stations.
Contact Information
Source: 240-56357424 MV and LV Switchgear Protection Standard (Rev 2.1).pdf (unknown){"name":null,"email":null,"phone":"016 457 5295","department":null,"address":null}
Evaluation Criteria
Source: 240-56357424 MV and LV Switchgear Protection Standard (Rev 2.1).pdf (unknown)While explicit commercial eligibility criteria (like B-BBEE, registration) are not stated in these technical excerpts, eligibility will be strongly determined by technical capability. Suppliers must have proven expertise in high-voltage electrical engineering, specifically in MV switchgear protection systems compliant with Eskom's stringent and proprietary standards. Experience working on Eskom Generation power stations is highly advantageous. Suppliers must be able to access and apply the latest controlled Eskom standards.
Technical Specifications
Source: 240-56357424 MV and LV Switchgear Protection Standard (Rev 2.1).pdf (unknown)This is a technical standard document, not a tender specification. The document outlines minimum protection requirements for MV and LV plant at Eskom power stations. It is intended as a standard for purchasing new protection schemes.
Compliance Requirements
Source: 240-56357424 MV and LV Switchgear Protection Standard (Rev 2.1).pdf (unknown)No specific compliance requirements (like CSD, tax, CIDB) are stated in the document.
Health & Safety
Source: 240-56357424 MV and LV Switchgear Protection Standard (Rev 2.1).pdfThe document is a technical standard focused on electrical protection, not a health and safety plan. However, it includes requirements that contribute to personnel and plant safety:
Description
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdfThis document is the Eskom Earthing and Lightning Protection Standard (240-56356396, Revision 2). It is not a tender document but a technical standard that defines requirements for the design, supply, installation, and testing of earthing and lightning protection systems at Eskom Generation power stations.
Primary objectives:
Scope: Applies to electrical and instrumentation systems within Eskom Generation.
The document includes extensive definitions, referenced standards, design principles, material specifications, installation guidelines, and testing requirements.
Evaluation Criteria
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdf (unknown)While this standard document does not list explicit tender eligibility criteria, it implies that eligible bidders must possess demonstrable expertise in high-voltage power station earthing and lightning protection systems. They must have the technical capability to fully comply with the extensive Eskom and South African National Standards (SANS) referenced within the document. Proven experience mitigating challenges like copper theft and corrosion in industrial settings is advantageous.
Technical Specifications
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdf (unknown)This is a technical standard document, not a tender specification. It defines the design, supply, installation, and testing requirements for earthing and lightning protection systems at Eskom Generation power stations.
Key requirements for bidders to note:
Limit touch and step potentials; provide a low impedance return path for fault currents.
Target maximum earth resistance for the complete system is 10 milli-ohms, maintainable up to 45m distances.
Protect installation against lightning, surges, spikes, and other induced interferences.
Methodology
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdfThe standard prescribes a detailed methodology for implementing earthing and lightning protection:
Experience & Qualifications
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdfThe document does not specify bidder experience or personnel qualifications. It defines the role of an 'Earthing Contractor' as a contractor appointed to install earthing conductors on cable racking and connect electrical/mechanical equipment to earth. It implies that contractors must have the skill to execute specialized connections (brazing, exothermic welding) which are material and skill-dependent.
Quality Management
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdfThe standard mandates rigorous testing, maintenance, and documentation to ensure system integrity:
Compliance Requirements
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdf (unknown)The document does not list standard tender compliance requirements (CSD, tax, B-BBEE, CIDB, etc.). It is a technical standard. Compliance is required with the extensive list of referenced technical standards and Eskom specifications, including:
Health & Safety
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdfThe core purpose of the earthing system is personnel safety. Key safety-related requirements include:
Section
Source: 240-56356396 Earthing and Lightning Protection Standard (Rev 2)_SIGNED.pdfThe document does not contain tender evaluation criteria. It is a technical standard. The extracted text appears to be fragmented and does not describe a scoring method for bid evaluation.
Description
Source: 240-68099512 Form A_Cat 1_ Rev 9.docxSubmission Guidelines
Source: 240-68099512 Form A_Cat 1_ Rev 9.docx (unknown)Returnable Documents: The tenderer must complete and sign the form to acknowledge and accept Eskom Supplier Quality Requirements as per 240-105658000 Specification and ISO 9001 Standard.
Evaluation Criteria
Source: 240-68099512 Form A_Cat 1_ Rev 9.docx (unknown)General
Technical
Description
Source: MV Switchgear Outside Plant 2026.zipEvaluation Criteria
Source: MV Switchgear Outside Plant 2026.zip (unknown)General
Technical
Technical Specifications
Source: MV Switchgear Outside Plant 2026.zip (unknown)Compliance Requirements
Source: MV Switchgear Outside Plant 2026.zip (unknown)Section
Source: MV Switchgear Outside Plant 2026.zipDescription
Source: ECC Outside plant MV switchgear upgrade.pdfImportant Dates
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Contact Information
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Submission Guidelines
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Returnable Documents
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Evaluation Criteria
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Contractor must complete Part 2 of Contract Data (to be provided at tender stage); have relevant experience in MV switchgear upgrades; comply with South African law; potentially require CIDB registration (if applicable); must not have conflicts of interest or engage in prohibited actions (corruption, fraud, etc.); joint ventures must declare structure and accept joint liability; must maintain B-BBEE status throughout contract period.
Technical Specifications
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Experience & Qualifications
Source: ECC Outside plant MV switchgear upgrade.pdfQuality Management
Source: ECC Outside plant MV switchgear upgrade.pdfPricing Schedule
Source: ECC Outside plant MV switchgear upgrade.pdfFinancial Requirements
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Compliance Requirements
Source: ECC Outside plant MV switchgear upgrade.pdf (unknown)Health & Safety
Source: ECC Outside plant MV switchgear upgrade.pdfEnvironmental
Source: ECC Outside plant MV switchgear upgrade.pdfContractual Terms
Source: ECC Outside plant MV switchgear upgrade.pdfImportant Dates
Source: Tender Advert Template MV Switchgear upgrade.pdf (TENDER)Contact Information
Source: Tender Advert Template MV Switchgear upgrade.pdf (TENDER)Submission Guidelines
Source: Tender Advert Template MV Switchgear upgrade.pdf (TENDER)Returnable documents are required but not specified in detail.
Evaluation Criteria
Source: Tender Advert Template MV Switchgear upgrade.pdf (TENDER)Tenderers must have a CIDB contractor grading of 8EP or 8ME or higher. Joint ventures are permitted if all members are CIDB registered, the lead partner meets the grading requirement (or is one level below), and the combined grading equals or exceeds 8EP/8ME.
Compliance Requirements
Source: Tender Advert Template MV Switchgear upgrade.pdf (TENDER)Requirements
Source: Tender Advert Template MV Switchgear upgrade.pdf (TENDER)Section
Source: Tender Advert Template MV Switchgear upgrade.pdf (TENDER)Description
Source: 240-77471499 Annexure B (3).docxThe tender pertains to the provision of Outside Plant MV Switchgear Upgrade at Arnot Power Station for a 3-year period. Compliance with Eskom’s OHS legal and other requirements is a critical component, as outlined in Annexure B (Acknowledgement Form).
Evaluation Criteria
Source: 240-77471499 Annexure B (3).docx (unknown)Companies must have experience in similar MV switchgear upgrade projects, ability to manage subcontractors effectively, proven OHS compliance track record, resources to execute 3-year contract, and willingness to align company processes with ESKOM's OHS requirements post-award.
Technical Specifications
Source: 240-77471499 Annexure B (3).docx (unknown)The tender requires compliance with Eskom’s Occupational Health and Safety (OHS) legal and other requirements. Key points include:
Compliance Requirements
Source: 240-77471499 Annexure B (3).docx (unknown)Compliance with Eskom’s OHS legal requirements is mandatory. This includes adherence to:
Important Dates
Source: Tender Advert Template Switchgear.pdf (TENDER)Briefing Session
Source: Tender Advert Template Switchgear.pdf (TENDER)Compliance Requirements
Source: Tender Advert Template Switchgear.pdf (TENDER)Requirements
Source: Tender Advert Template Switchgear.pdf (TENDER)Section
Source: Tender Advert Template Switchgear.pdf (TENDER)Description
Source: 240-143485806 Gx MV Protection std.pdfThis document is an Eskom Generation standard for Medium Voltage Protection of auxiliary plant. It provides:
Evaluation Criteria
Source: 240-143485806 Gx MV Protection std.pdf (unknown)While not explicitly stated in this standard, eligibility for the related tender would implicitly require: Proven expertise in Eskom's MV protection philosophy and standards; Ability to supply and configure IEDs from Eskom's approved list (ref. 240-56227589); Engineering personnel qualified to perform protection setting calculations per this guide; Compliance with all normative references (e.g., IEC 61800-4, Eskom engineering procedures); Capability to execute work under 'Controlled Disclosure' classification.
Technical Specifications
Source: 240-143485806 Gx MV Protection std.pdf (unknown)This document is a technical standard for Medium Voltage Protection in Eskom Generation power stations. It outlines the protection philosophy, requirements, and design principles for electrical protection systems on medium voltage (MV) reticulation. Key points for bidders:
Methodology
Source: 240-143485806 Gx MV Protection std.pdfThe document outlines the methodology for MV protection design and implementation:
Quality Management
Source: 240-143485806 Gx MV Protection std.pdfThe document specifies requirements for supervision and testing to ensure protection quality and reliability:
Compliance Requirements
Source: 240-143485806 Gx MV Protection std.pdf (unknown)The document references several normative standards and procedures that must be applied. Bidders must ensure compliance with:
Health & Safety
Source: 240-143485806 Gx MV Protection std.pdfThe document includes safety-related requirements for protection and control systems:
Contractual Terms
Source: 240-143485806 Gx MV Protection std.pdfThe document references normative standards and procedures that form part of the contractual framework. Bidders must apply:
Description
Source: 240-56030406 RMU standard.pdfThis specification standardises and rationalises medium voltage Ring Main Units (RMUs) and IRTU fitted RMUs for Eskom, including remote terminal units and protection systems for free-standing indoor/outdoor applications. It covers distribution automation, IPP applications, high-risk enclosures, and 36 kV units for Generation and Distribution.
Submission Guidelines
Source: 240-56030406 RMU standard.pdf (unknown)Returnable Documents: The full Technical Schedules B (including Test Schedules and Deviation Schedules) must be completed and submitted together with Technical Schedules A for approval at the time of tender. This includes individual RMU and IRTU fitted RMU item Technical Schedules.
Evaluation Criteria
Source: 240-56030406 RMU standard.pdf (unknown)Suppliers must be conversant with and comply fully with Specification 240-56030406. They must obtain all necessary supporting documents. Suppliers must have ISO 9001 Quality Management Systems (normative reference). Any deviation constitutes non-conformance unless agreed in advance by a delegated Eskom Cable Systems Specialist based on sound engineering judgement. Proof of performance for protection systems up to the circuit-breaker's rated short-circuit breaking current is required. SPRs using external DIP switches/potentiometers for settings are not accepted. Configuration software must be provided at no extra cost and be compatible with specified Windows OS.
Technical Specifications
Source: 240-56030406 RMU standard.pdf (unknown)This specification covers Eskom’s requirements for new factory-assembled Ring Main Units (RMUs) and Integrated Remote Terminal Unit (IRTU) fitted RMUs rated for three-phase cable systems from 3.6 kV to 36 kV, for freestanding indoor or outdoor operation at 50 Hz. It distinguishes between inland and coastal applications and excludes bulk metering kiosks. Key requirements include compliance with SANS 1874 and other referenced standards, specific configurations, lightning impulse withstand levels, cable test facilities, remote tripping, fuse-link specifications, protection equipment (SPR or IED), RTU requirements, DC supply, control plant enclosure, plant status controls, wiring, LV AC power supply, MV cable termination enclosures, gas pressure indication, live circuit indication, earth fault indication, padlock protection, concrete plinths, corrosion protection, documentation, testing, and marking.
Quality Management
Source: 240-56030406 RMU standard.pdfSuppliers must comply with ISO 9001 and other referenced standards. Specific requirements include software/firmware version control, configuration management, test reports, and vendor responsibilities for setup and testing.
Compliance Requirements
Source: 240-56030406 RMU standard.pdf (unknown)All RMUs and IRTU fitted RMUs must comply with SANS 1874 and this specification, with this specification taking precedence in case of conflict. Suppliers must be conversant with and comply with all requirements; no deviations are accepted without prior agreement from Eskom. The process for monitoring uses technical evaluation criteria and technical schedules A and B as per SANS 1874.
Health & Safety
Source: 240-56030406 RMU standard.pdfSafety requirements include internal arc classification testing per SANS/IEC 62271-202 for outdoor RMUs and SANS/IEC 62271-200 for indoor units, with submission of type test reports and videos for Eskom safety review. Live circuit indication and earth fault indication are mandated.
Environmental
Source: 240-56030406 RMU standard.pdfEnvironmental considerations include corrosion protection based on inland (medium pollution) or coastal (very heavy pollution) classifications per SANS 60815-1, with specific corrosivity ratings and detailed specifications referenced.
Contractual Terms
Source: 240-56030406 RMU standard.pdfThe specification outlines technical requirements for RMUs and IRTU fitted RMUs, including configurations, testing, protection systems, wiring, power supply, enclosures, and documentation. It references Eskom standards and drawings, with no explicit contractual terms like duration or penalties provided.
Section
Source: 240-56030406 RMU standard.pdfThe evaluation includes detailed protection requirements for IRTU fitted RMUs with Protection IEDs, covering harmonic restraint, overcurrent and earth fault functions, directional power, live load blocking, negative phase sequence, frequency and voltage protection, measurement functions, event recording, configuration software, and sensor requirements. Suppliers must provide specific technical details in schedules.
Description
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdfImportant Dates
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Briefing Session
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Contact Information
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Submission Guidelines
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Evaluation Criteria
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Tenderer (or JV partners) must not be under any restriction to do business with Eskom or the state; not have nationality from a sanctioned country; not submit multiple tenders (except for system limits); JV must have joint and several liability; no conflicts of interest; not restricted by National Treasury, Eskom, or on Tender Defaulters list; must have required CIDB grading of 8EP or 8ME or higher (for JV, lead partner must meet grading and combined grading must equal or exceed).
Technical Specifications
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Experience & Qualifications
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdfQuality Management
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdfPricing Schedule
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdfFinancial Requirements
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Compliance Requirements
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdf (TENDER)Health & Safety
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdfEnvironmental
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdfContractual Terms
Source: Invitation to Tender (ITT) - Switch Gear Upgrade.pdfDescription
Source: TENDER~3.PDFImportant Dates
Source: TENDER~3.PDF (TENDER)Contact Information
Source: TENDER~3.PDF (TENDER)Submission Guidelines
Source: TENDER~3.PDF (TENDER)Evaluation Criteria
Source: TENDER~3.PDF (TENDER)All tenderers eligible, but scoring and award depend on B-BBEE status and price. Tenderers without valid B-BBEE docs can only score out of 80 for price (lose all 10 B-BBEE points). Non-compliance with CIDB CSDG or local content documentation (SBD 6.2, Annex C) renders tender non-responsive. Must meet designated sector local content threshold (90% for electrical cables).
Technical Specifications
Source: TENDER~3.PDF (TENDER)Methodology
Source: TENDER~3.PDFPricing Schedule
Source: TENDER~3.PDFFinancial Requirements
Source: TENDER~3.PDF (TENDER)Compliance Requirements
Source: TENDER~3.PDF (TENDER)B-BBEE Requirements
Source: TENDER~3.PDF (TENDER)Contractual Terms
Source: TENDER~3.PDF (TENDER)Special Conditions
Source: TENDER~3.PDF (TENDER)Requirements
Source: TENDER~3.PDF (TENDER)Section
Source: TENDER~3.PDFDescription
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdfProject: Replacement of obsolete MV switchgear at Arnot Power Station.
Submission Guidelines
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdf (unknown)To avoid disqualification, you must submit the following returnable documents:
Returnable Documents
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdf (unknown)Mandatory returnable documents:
Evaluation Criteria
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdf (unknown)Mandatory criteria: 1) Submission of all required compliance schedules and documentation. 2) Proof of switchgear compliance with internal arc protection standards (IEC 62271-200). 3) All major equipment must be from the OEM or backed by a license agreement valid for the contract duration. 4) Demonstrated experience with similar projects and technology.
Technical Specifications
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdf (unknown)Project: Replacement of outside plant MV switchgear at Arnot Power Station over 3 years.
Scope includes:
Key technical drivers:
New switchgear must:
Referenced standards and documents:
Methodology
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdf (unknown)Qualitative evaluation includes methodology aspects:
Experience & Qualifications
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdfBidder experience requirements:
Quality Management
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdfIf the type testing laboratory used is not a member of Short-circuit Test Liaison (STL), you must provide proof of the laboratory's compliance with ISO/IEC 17025 requirements.
Compliance Requirements
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdf (unknown)Mandatory compliance requirements:
Note: The document is a Controlled Disclosure tender technical evaluation strategy. It references Eskom procurement policy and generation tender evaluation procedure.
Health & Safety
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdfSafety critical issues with existing switchgear:
The replacement project will address these to ensure a safe and stable electrical supply with compliant, advanced arc mitigation systems.
Contractual Terms
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdfThe replacement project aims to eliminate obsolescence, improve reliability, and ensure a safe, stable electrical supply. New switchgear must comply with internal arc protection standards and incorporate advanced arc mitigation systems.
Requirements
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdf (unknown)Mandatory submission requirements:
Section
Source: MV Switchgear Technical Evaluation Criteria Rev 2..pdfThis section details the technical evaluation strategy. See the main evaluationCriteria section for structured criteria and scoring.
Description
Source: 240-56227589 list of approved electronic devices.pdfThis document is Eskom's 'List of Approved Electronic Devices to be used on Eskom Power Stations' (Standard 36-726).
Evaluation Criteria
Source: 240-56227589 list of approved electronic devices.pdf (unknown)Suppliers must demonstrate the ability to supply and support equipment from the approved manufacturers listed in the standard's appendices. Technical proposals must align with the device functions and communication protocols specified for each application. Suppliers are responsible for ensuring any proposed device firmware/hardware versions are compatible with the approved versions listed, as per notes in section 3.2.
Technical Specifications
Source: 240-56227589 list of approved electronic devices.pdf (unknown)This document is Eskom's standard list of approved electronic devices for power station electrical plant.
Quality Management
Source: 240-56227589 list of approved electronic devices.pdfThe document defines quality assurance processes for electronic devices.
Compliance Requirements
Source: 240-56227589 list of approved electronic devices.pdf (unknown)The document specifies technical compliance requirements for electronic devices used on Eskom power stations.
Environmental
Source: 240-56227589 list of approved electronic devices.pdfThe document specifies environmental testing requirements for electronic devices.
Description
Source: Life-Saving Rules (2).pdfImportant Dates
Source: Life-Saving Rules (2).pdf (unknown)Evaluation Criteria
Source: Life-Saving Rules (2).pdf (unknown)To be eligible to work on Eskom sites, a contractor must: 1. Formally integrate these Life-Saving Rules into their site safety management system. 2. Have a documented process for training all site personnel on these rules and obtaining signed acknowledgements. 3. Have a compliant disciplinary process to address violations within 5 working days. 4. Ensure all operational procedures align with the extensive referenced normative documents (e.g., Plant Safety Regulations, High Voltage Operating Regulations, Working at Heights Standard).
Technical Specifications
Source: Life-Saving Rules (2).pdf (unknown)Methodology
Source: Life-Saving Rules (2).pdfQuality Management
Source: Life-Saving Rules (2).pdfCompliance Requirements
Source: Life-Saving Rules (2).pdf (unknown)Health & Safety
Source: Life-Saving Rules (2).pdfSection
Source: Life-Saving Rules (2).pdfDescription
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdfEvaluation Criteria
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdf (unknown)Suppliers must provide cables that comply with SANS standards and Eskom specifications. All cable offerings must carry valid product type tests according to relevant SANS standards. Documentation including type test reports must be submitted at tender enquiry. Cables must meet specific construction requirements including voltage ratings, conductor classes, insulation types, and fire performance standards.
Technical Specifications
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdf (unknown)Quality Management
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdfCompliance Requirements
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdf (unknown)Health & Safety
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdfContractual Terms
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdfSection
Source: 240-56227443 Generation Requirements for Control and Power Cables for Power Stations Standard.pdfSets the constitutional standard for fair, equitable, transparent, competitive and cost-effective public procurement.
Relevant because this is a South African public-sector procurement opportunity.
Act 5 of 2000
Covers preferential procurement and preference-point systems used in public tenders.
Relevant because this is a South African public-sector procurement opportunity.
Act 12 of 2004
Supports anti-corruption controls and supplier integrity in procurement processes.
Relevant because this is a South African public-sector procurement opportunity.
Act 28 of 2024
Provides the national framework for public procurement across government.
Relevant because this is a South African public-sector procurement opportunity.
Act 2 of 2000
Supports access to tender records, award decisions and public-sector procurement information.
Relevant because this is a South African public-sector procurement opportunity.
Act 3 of 2000
Supports lawful, reasonable and procedurally fair administrative tender decisions.
Relevant because this is a South African public-sector procurement opportunity.
These rules are linked to the work category, industry, or regulated service area.
Act 38 of 2000
Important for public-sector construction and infrastructure tenders that require contractor grading or construction procurement standards.
Relevant because this tender appears to involve engineering, technical design, maintenance, or regulated built-environment work.
Act 85 of 1993
Sets health and safety duties for contractors, employers and service providers working on public-sector sites.
Relevant because this tender appears to involve engineering, technical design, maintenance, or regulated built-environment work.
Act 46 of 2000
Relevant where professional engineering services or regulated engineering work may be required.
Relevant because this tender appears to involve engineering, technical design, maintenance, or regulated built-environment work.
Address
Arnot Power Station - Arnot Power Station - RIETKUIL - 1087
Source confidence
High source confidence
Official source
eTenders.gov.za
Documents found
19
Last checked
22 Jul 2026
AI status
Enhanced
Data conflicts
None detected
This tender has strong source evidence, including source metadata and supporting tender information synced from the government tender portal.
Tenders SA is not the issuing authority. All tenders are automatically synced from the official government tender portal. Always confirm final submission details, closing dates, briefing sessions, eligibility requirements, and documents on the official government portal before applying.
Key Personnel
Provinces Active
Industries
Financial